Measurement range r.H. |
0-100% r.H. |
Measurement range temp. |
-20...+80°C |
Accuracy humidity |
±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C) |
Temperature dependency |
±0,02% r.H. / K (voltage output), ±0,04% r.H. / K (current output) |
Long term stability |
±1%/year |
Sensor |
capacitive humidity sensor; Pt100, Pt500, Pt1000, Ni1000, KTY, NTC, LM235Z (other on request) |
Sensor protection |
screwable stainless steel sinter filter, condensation protection by heating function in the range of 95...99% r.H. |
Flow rate |
< 2 m/s |
Supply voltage analog 0-10 V |
24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA |
15...36 V DC (Ubmin = 15 V + RLoad*0,02A) |
Current consumption at 0-10 V |
typ. 10 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay |
Current consumption at 4-20 mA |
max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay |
Analogue output 0-10 V |
3-wire connection, load current < 0,1 mA |
Analogue output 4-20 mA |
2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub - 15 V) / 0,02 A |
Alarm output |
1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay |
2% of the selected scaling (without display), 0,5...5% of the selected scaling adjustable (with display) |
Electrical connection |
screw terminals max. 1,5 mm² |
Housing |
Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Cable gland |
PG11 high-strength cable gland with strain relief |
Display |
optional LCD display with backlight on/off/auto |
Material |
Protection tube: stainless steel V2A |
Dimensions |
Housing: L 89 x W 80 x H 47 mm, Protection tube: Ø 16 x 40 mm |
Protection type |
Housing/electronic: IP65, Sensor: IP30 |
Protection class |
III |
Working range r.H. |
0...98% r.H. in contaminant-free, non-condensing air |
Working temperature |
Probe: -20...+80°C, Electronic: -20...+70°C |
Storage temperature |
-20...+50°C |
Installation |
screw fastening |
Approvals |
CE, EAC, RoHS |