| Supply voltage for 0-10 V: | 24 V AC/DC (± 5%) |
| Analogue output 0-10 V: | 3-wire connection, min. load resistance 100kOhm |
| Supply voltage for 4-20 mA: | 10...30V DC, depends on liability (Ubmin = 10V + Rload*0,02A) |
| Analogue output 4-20 mA: | 2-wire connection (transmitter), max. Rload(Ohm) = (+Ub-10V)/0,02A |
| Accuracy: | ±0,2K + max. ±3% eigenvalue |
| Measurement range: | 16 measuring ranges per DIP switch selectable |
| Measurement range options: | -50...+50°C, -50...+150°C, -30...+70°C, -20...+50°C, -20...+80°C, -20...+120°C, -20...+150°C, 0...+50°C, 0...+100°C, 0...+150°C, 0...+200°C (other on request) |
| Working temperature sensor: | -30...+75°C |
| Working temperature electronic: | -30...+70°C |
| Working range r.H.: | 0...98%r.H., without condensation |
| Sensor: | Pt100 DIN EN 60751, Class B |
| Electrical connection: | screw terminals max. 1,5mm² |
| Cable gland: | PG11 high-strength cable gland with strain relief |
| Mounting: | screw fastening |
| Housing: | polyamide (synthetic) with snap closing screws |
| Colour: | white (like RAL 9010) |
| Protection type: | IP65 |
| Dimension: | L 64 x W 58 x H 34,5mm |
| Probe cable: | 2m PVC cable (other on request) |
| Globe: | black aluminium globe Ø 70mm |
| Standards: | CE-conformity, EMC according to EN 61326-1 2006, EMV directive 89/336/EWG |
| Storing temperature: | -20...+50°C |
| Display: | optional LCD-Display, to display the actual-temperature |